Product number:
20401516
Product information "Vacuum regulator C 2214"
The C 2214 is designed for individual operation. For use on gas drums, a heated droplet separator is optionally available on the pressure side in the inlet valve of the C 2214. A safety blow-off valve is integrated and prevents an impermissible increase in pressure in the downstream vacuum line system. The quantity of gas dosed can be optimally adjusted on the C 2214 using a dosing valve and flow meter.
Features & advantages
- Throughput capacity with chlorine gas: up to 4 kg/h
- Residual pressure protection: Prevents the chlorine cylinder from being completely evacuated to prevent corrosion caused by moisture in the air
- Filter: To protect the valve from dirt particles from the chlorine cylinder or the connection area
- Cylinder pressure gauge: For displaying the pressure in the chlorine tank
- Integrated safety blow-off valve
- Flow meter with manual setting
- Gas filter
- Compact design
- Available with all standard gas connections
Blow-off connection:: | Hose clamp connection 8/12 |
---|---|
Dosing connection:: | Schlauchklemm-Anschluss 8/12 |
Entrance:: | Union nut BSW 1" - DIN 477 |
Flow meter:: | 1 - 25 g/h |
Function-2: | Overpressure of the gas containers to negative pressure [vacuum]. |
Function-3: | When the operating vacuum is removed, the inlet valve closes and |
Function-4: | prevents the flow. |
Function-5: | Suitable for dry chlorine gas [purity > 99.5%]. |
Functions:: | Der Vakuumregler dient zur Reduzierung des Gasdrucks vom |
MATCHCODE: | 0204V11N1N0025L1B |
Medium:: | Chlorine gas |
Pressure gauge:: | 0 - 16 bar [g] |
Residual pressure safety device:: | 1 bar |
Type:: | C 2214 |